Product display
contact us
Sales Hotline:
Contact Hotline
0755-83704966 18824317447
Fax:0755-83704966

E-mail:admin@eton-tech.com

Company address:Building 3, No. 16, Guangming Road, Shiyan street, Baoan District, Shenzhen, China
 

Product Introduction:
 This product is capable of both cooling and heating functions. The cooling function effectively addresses issues such as thermal runaway, severe capacity degradation, and product lifespan reduction caused by excessive temperature during battery charging and discharging. The heating function effectively resolves the problem of batteries not being conducive to charging and discharging in low-temperature environments and cold regions, ensuring normal battery charging and discharging, and allowing the battery to operate efficiently within an appropriate temperature range.

  The product includes a refrigeration and heating circuit and a battery pack cooling water circuit, with the two circuits exchanging heat through a plate heat exchanger (Chiller). The refrigeration circuit generates low temperatures, and the battery pack cooling water circuit cools the battery pack, after which the cooling water is heated and then cooled again through the plate heat exchanger, achieving dynamic equilibrium and ultimately cooling the battery. The refrigeration system module consists of components such as a compressor, condenser, plate heat exchanger, and throttle valve; the water circuit module consists of components such as a water pump, PTC heater, and water pipes!


5KW.png

A.png

Core advantages:

Efficient heat dissipation: The specific heat capacity of liquid is much higher than that of air, allowing for more efficient transfer of large amounts of heat, making it particularly suitable for thermal loads at the 5kW level.

Compact layout: The "horizontal" design reduces the overall height, making it suitable for 19-inch standard cabinets, equipment bottom installation, or situations where space height is limited.

Low noise: Compared to large fans with equivalent cooling capacity, liquid cooling systems primarily generate noise from the water pump and a small number of fans, making them generally quieter.

Precise temperature control: It can achieve liquid temperature control with an accuracy of ±0.5°C or even higher, ensuring that the cooled equipment is maintained at its optimal operating temperature.

Long-distance heat transfer: The cooling liquid can be transported through pipelines over long distances, discharging the heat to a more suitable location (such as outdoors), thereby optimizing the environment of the computer room.

Product  functional features:

This product is capable of achieving both cooling and heating functions. The cooling function effectively addresses the issue of overheating caused by batteries during the charging and discharging process

Issues such as thermal runaway, severe battery capacity degradation, and product lifespan attenuation; the heating function effectively addresses the challenges posed to batteries in low-temperature environments and cold regions

Regarding the issue of charging and discharging, it ensures that the battery can be charged and discharged normally, allowing it to operate efficiently within an appropriate temperature range.

This product includes a refrigeration and heating circuit as well as a battery pack cooling water circuit, with heat exchange between the two circuits facilitated by a plate heat exchanger (chiller); manufacture

The cold loop generates low temperature, and the battery pack cooling water loop cools the battery pack, after which the cooling water is heated and then cooled again through a plate heat exchanger

Achieve dynamic equilibrium and ultimately achieve cooling of the battery. The refrigeration system module consists of components such as a compressor, condenser, plate heat exchanger, and throttle valve

Composition: The water circuit module consists of components such as a water pump, PTC heater, and water pipes.

main components:

liquid cooling pipe

管道.png

liquid-cooled plate:

板.png

Detailed specifications:

Parameter requirements Remarks

Overall dimensions (depth * width * height) 900*700*245

Mass (excluding refrigerant) ≤ 80kg

Installation method: Internal installation

Application environment: Outdoor type

Operating environment range: -40℃~+55℃

Storage environment range: -40℃~+85℃

Noise level: <65dB(A)

IP protection level: IPX5

Corrosion protection level C3H

Refrigerant: R134A

Refrigerant: ethylene glycol aqueous solution

RoHS certification: Yes

Cooling capacity @ L40/W18: 5.2 kW

Heating capacity W10℃ 2.5kW

Water outlet temperature: 18℃

Rated circulating water flow rate: 40/min@160kPa

Refrigeration input power

@L40/W18 2.24 kW

Power supply range: 1/PEAC 220V 50Hz/60Hz

Maximum current: 12.14A

Main distribution circuit protection mechanism: Fuse or miniature circuit breaker

Operating ambient humidity range: 5%—95% (with condensation)

Operational altitude < 4000m

Handling method: Forklift handling or lifting

Seismic grade: Magnitude 8 intensity

Paint film adhesion: Class 1 according to GB/T9286, no peeling observed in cross-cut test

Insulation material: non-toxic, harmless, odorless, and non-hygroscopic

Water pipe installation method NW26

Backup requirement: Single system

Flame retardant grade: PCB board: UL94-V0;

Other isolation types: UL94-V;

Thermal insulation category: UL94-HB-F

Control function Local control

Maintenance method: outdoor maintenance

The lifespan of the entire machine is >10 years

Control accuracy <1℃

Alarm display: available

Over-temperature protection during heating is available

Power overvoltage and undervoltage protection is available

Compressor high pressure protection is available

Incoming call auto-start function is available

Start delay function is available

Communication interface: CAN2.0 or RS485

Tightness of refrigeration system: Refrigerant leakage <3g/year


Application Scenario:


High-performance computing servers/GPU servers: Address the challenge of centralized cooling for CPUs and GPUs.

High-power laser processing equipment: Provides a stable and low-temperature operating environment for the laser device.

Power electronic devices: such as frequency converters, inverters, radar transmitters, etc.

Medical and scientific research equipment: MRI, accelerator, spectrometer, and other temperature-sensitive equipment.

Communication core equipment: core network equipment for 5G base stations, high-end routers, etc.

261index.jpg

522首页.jpg