Product Introduction:
This product is capable of both cooling and heating functions. The cooling function effectively addresses issues such as thermal runaway, severe capacity degradation, and product lifespan reduction caused by excessive temperature during battery charging and discharging. The heating function effectively resolves the problem of batteries not being conducive to charging and discharging in low-temperature environments and cold regions, ensuring normal battery charging and discharging, and allowing the battery to operate efficiently within an appropriate temperature range.
The product includes a refrigeration and heating circuit and a battery pack cooling water circuit, with the two circuits exchanging heat through a plate heat exchanger (Chiller). The refrigeration circuit generates low temperatures, and the battery pack cooling water circuit cools the battery pack, after which the cooling water is heated and then cooled again through the plate heat exchanger, achieving dynamic equilibrium and ultimately cooling the battery. The refrigeration system module consists of components such as a compressor, condenser, plate heat exchanger, and throttle valve; the water circuit module consists of components such as a water pump, PTC heater, and water pipes!


Core advantages:
High power: Capable of meeting the severe heat dissipation challenges of the 8kW level.
High efficiency: Utilizing liquid heat exchange, the efficiency is far superior to air cooling.
Ultra-quiet: Optimized design brings a quiet working environment.
Easy integration: Horizontal chassis design, perfectly fitting into standard cabinets.
Intelligentization: Precise control and remote monitoring, convenient operation and maintenance.
Product functional features:
This product is capable of achieving both cooling and heating functions. The cooling function effectively addresses the issue of overheating caused by batteries during the charging and discharging process
Issues such as thermal runaway, severe battery capacity degradation, and product lifespan attenuation; the heating function effectively addresses the challenges posed to batteries in low-temperature environments and cold regions
Regarding the issue of charging and discharging, it ensures that the battery can be charged and discharged normally, allowing it to operate efficiently within an appropriate temperature range.
This product includes a refrigeration and heating circuit as well as a battery pack cooling water circuit, with heat exchange between the two circuits facilitated by a plate heat exchanger (chiller); manufacture
The cold loop generates low temperature, and the battery pack cooling water loop cools the battery pack, after which the cooling water is heated and then cooled again through a plate heat exchanger
Achieve dynamic equilibrium and ultimately achieve cooling of the battery. The refrigeration system module consists of components such as a compressor, condenser, plate heat exchanger, and throttle valve
Composition: The water circuit module consists of components such as a water pump, PTC heater, and water pipes.
main components:
liquid cooling pipe

liquid-cooled plate:

Detailed specifications:
Project: Parameters
Dimensions (Depth * Width * Height): 1100-250.5 * 960nm
Quality (excluding refrigerant): ≤ 120kg
Installation method: internal installation
Application environment: Outdoor type
Working environment range: -40 ℃~+55 ℃
Storage environment range: -40 ℃~+85 ℃
Noise level: < 65dB (A)
IP protection level: IPX5
Anti corrosion grade: C3H
Refrigerant: R134A
Refrigerant: Ethylene glycol aqueous solution
RoHS certification: Yes
Cooling capacity @ L40/W18: 8.6kW
Heating capacity W10 ℃: 3.0kW
Outlet temperature: 18 ℃
Rated circulating water flow rate: 40/ min@160kPa
Cooling input power @ L40/W18: 3.58 kW
Power range: 1/PEAC220V50Hz/60Hz
Maximum current: 17.3A
Main distribution circuit protection mechanism: fuse or miniature circuit breaker
Operating environment humidity range: 5% -95% (with condensation)
Usage altitude:<4000m
Handling method: Forklift handling or lifting
Seismic grade: Intensity level 8
Adhesion of paint film: GB/T92861 level, no peeling at 100 grids
Thermal insulation material: non-toxic, harmless, odorless, non hygroscopic
Installation method of water pipe: NW26
Backup requirement: Single system
Flame retardant grade PCB board: UL94-V0; Other isolation categories: UL94-V; Insulation class: UL94-HB-F
Control function: Local control
Maintenance method: Outdoor maintenance
Whole machine lifespan:>10 years
Vibration: Complies with GB/T19183.5-2003
Transport vibration: meets GB/T3873 road transport test for packaging weighing over 100kg
Control accuracy:<1 ℃
Alarm display: equipped with
Heating over temperature protection: equipped with
Power overvoltage and undervoltage protection: equipped with
Compressor high pressure protection: equipped with
Call auto start function: equipped with
Start delay function: equipped with
Communication interface: CAN2.0 or RS485
Sealing of refrigeration system: refrigerant leakage rate<3g/year